MX350 Controller
The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, graphical controls and LED indicators reduce external components and wiring in addition to providing local control and access to system information. Multiple communication protocols allow simple integration into monitoring and control systems.
Controller Specifications
Voltage Unbalance on Dropout for Source 1 and Source 2
Delay NeutralTransition Time Delays (DT,DW)
Control Power
Undervoltage Dropout for Source 1 and Source 2
Undervoltage Restore for Source 1 and Source 2
Overfrequency Dropout for Source 1 and Source 2
Source Sensing
Delay for Engine Cool Down (U)
Underfrequency Restore for Source 1 and Source 2
Load Control Relay Contacts (2)
Overvoltage Dropout for Source 1 and Source 2
Voltage Unbalance for Restore for Source 1 and Source 2
Storage Temperature
Underfrequency Dropout for Source 1 and Source 2
Overfrequency Restore for Source 1 and Source 2
Delay Transfer to Nonpreferred Source (W)
Operating Temperature Ambient
Communications Interface - Optional
Overvoltage Restore for Source 1 and Source 2
Load Control Relay Contacts (1)
Technical Summary
Rating Range
Transfer Type
Switch Type
Standard Equipment:
-
- Status Leds For:
-
- Transfer Inhibit
- Active Alarms
- Source 1 and 2 Availablity
- Source 1 and 2 Connected
- Time Delay Active
-
- Graphical Display:
-
- Color graphical display with USB Calibration/programming port and Embedded Help
- Displays 256 time-tagged events with 1 ms resolution
- Monitors over/under frequency, voltage conditions, frequency imbalance, and phase rotation
- Provided detailed outage,test,and diagnostic reports
-
- Ranges Of Controls / Metering:
-
- Programmable generator exerciser
- Synchroscope
- Contacts for Source 1 and Source 2 position indication as well as remote load test signals, and engine start delay
- Source 1 and Source 2 In-phase monitor
- Neutral, Engine Start, and Engine stop time delay timers
-
- Testing And Certification
-
- Conforms to EN 60947-1, EN 60947-6-1, EN 60255-26 (EN 50263), EN 5502 / CISPR22 / EN 61000-6-2 / EN 61000-6-4
- Tested in accordance with:
IEC 60068-2-30
IEC 60068-2-1
IEC 60068-2-2
IEC 60255-22-1
IEC 60255-22-2
IEC 60255-22-3
IEC 60255-22-4
IEC 60255-22-5
IEC 60255-22-6
IEC 60255-25
IEC 60529; IP54 (front),IP20(back)
IEC 61000-4-11 - Quality System:
Manufactured under an ISO 9001 Registered Program
Optional Equipment:
-
- Option Package A:
-
- Four (4) programmable inputs and four (4) outputs assignable to additional ATS features
- Expanded diagnostics, high-speed 256 event capture, 365 days
- Monitoring Software (local or remote), USB interface for uploading and downloading setup parameters
- Full function ATS control with full sensing and control capabilities
- Full complement of programmable ATS control switches AUTO / MAN, Preferred Source selector,Commit / No Commit Xfer, Transition Mode Select for Closed Transition switch models)
-
- Option Package B:
-
- Waveform capture, ten (10) channels, up to 256 cycles each sixteen (16) samples / sec.
- Ten (10) customer programmable digital and ten (10)analog alarms.
- Includes Option Package A features, plus
- Auto Load Shed with voltage, frequency and kW triggers.
- Twenty (20) channel data logger, customer configurable sample period from one (1) cycle to sixty (60) minutes.
-
- Option Package C:
-
- Includes Option B features, plus
- Four (4) additional inputs and outputs (totaling eight (8) in & eight (8) out)
-
- Option Package D:
-
- Customized user control logic
- Includes Option Package C features, plus
- Four (4) additional inputs and outputs (totaling twelve (12) in & twelve (12) out)
-
- Option Package M:
-
- Configuration for Manual Operation only (Non-Automatic)
Contact Us
Get A Quote
Thank you for your interest in Mustang Cat. We are here to help you in any way that we can. If you have a question, need equipment advice or just need additional information, we want to hear from you. You can email, phone or fill out the form below and we will be happy to connect with you.